Product Introduction
The MWD1006L is a gas detection module based on the NDIR infrared absorption technology. It uses a single light source and a single-channel detector. The sampling method use self-diffusing. MWD1006L is suitable for detecting carbon dioxide concentration in indoor and outdoor air.
Main Application
MWD1006L can be widely used in air conditioning and fresh air control, indoor air quality monitoring, agricultural and animal husbandry production process monitoring, and can be installed in intelligent buildings, ventilation systems, controllers, wall mounted application, robots, automobiles and other applications. It can also be used for air quality monitoring in small spaces.
Sensor Module Characteristics
● Zero point self-calibration function
● Ultra-low power consumption
● Anti-interference from moisture
● Multiple output interfaces selection: UART, PWM , IIC and analog voltage output (adjustable)
● Wide temperature compensation range
For more information, Please check our product datasheet or send the consultation to us.
Hot Tags: Infrared CO2 Detection Module MWD1006L, China Infrared CO2 Detection Module MWD1006L manufacturers, suppliers, factory, electronic nose e nose , portable natural gas leak detector, fixed gas monitor, PM2 5 Particle Sensor Module, Customizable Thin Film Pressure Sensor, e nose device
Product Specifications
1 Working conditions
|
Item |
Symbol |
Value |
Unit |
|
Storage temperature |
T g |
-20 to 80 |
°C |
|
Operating temperature |
T A |
-10 to + 5 0 |
°C |
|
Working humidity |
H A |
0 to 90 |
% RH |
|
Work Pressure |
P A |
0.8 to 1.2 |
atm |
2 Electrical characteristics
|
Item |
Symbol |
Min |
Typical |
Max |
Unit |
|
Powered by |
V s |
4.5 |
5 |
5.5 |
V |
|
Maximum current |
I max |
120 |
150 |
mA |
|
|
Average current |
I ave |
30 |
36 |
90 |
mA |
3 Technical indicators
|
Item |
Min |
Typical |
Max |
Unit |
|
|
Range * |
5000 |
- |
ppm |
||
|
Measurement accuracy |
±50ppm or ±5% of the true value, whichever is greater |
ppm |
|||
|
Resolution |
1 |
ppm |
|||
|
Response time(T90) |
By diffusion |
- |
120 |
- |
Second |
|
Repeatability |
50% FS |
- |
<±5% of measured value |
- |
|
|
Life time |
3 |
5 |
10 |
Year |
|
Remark: * Range can be customized
4 Module size

Note: Unit: mm